Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/24/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service entrance is not per code.| 215* PLEASE CORRECT 1. THE NIPPLES INTO THE GUTTER MUST BE GROUND BONDED. ADD BUSHINGS AND GROUND TO GUTTER. 2. THE GROUNDING ELECTRODE CONDUCTOR MUST TERMINATE AT ONE OF THE PANELS NEUTRAL BAR THEN RUN GROUND WIRE PANEL TO PANEL TO GUTTER ( GROUND BAR) ( NOT NEUTRAL, POLARIS, LUG) 3. THE COVER NEEDS FURTHER WORK TO MOUNT SAFELY ON GUTTER. LEAVE NO SHARP EDGES. CORRECT & RECALL 6X GUTTER WOULD HAVE BEEN BETTER. |