Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/25/2008 | ELECTRIC - FINAL | Approved | ||
| 02/04/2008 | ELECTRIC - FINAL | Not ready for Inspection | CONTRACTOR TO MAKE CORRECTIONS BEFORE RECALLING THIS INSPECTION. NEW CONTRACTOR HAS TAKEN OVER JOB AFTER PREVIOUS OWNER ALLOWED THIS PERMIT TO EXPIRE. | |
| 05/24/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. FINISH PREVIOUS NOTES ITEMS 2. MAIN BREAKER TO HAVE MANUFACTURERS HOLD DOWN. |
|
| 05/18/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* IT LOOKS LIKE SOME CORRECTIONS HAVE NOT BEEN MADE. CALL RICK H. TO SCHEDULE THIS INSPECTION WITH HIM. HIS NUMBER IS 909-4749 |
|
| 05/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CALLED AHEAD AS REQUESTED NO ANSWER -- PLEASE RECALL AND LEAVE MESSAGE. |
|
| 11/30/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*PLEASE VERIFY GAS & WATER BONDING NO ENTRANCE THRU METER SECTIONOF ALL IN ONE SEAL ENTRANCES ABOVE CURRENT CARRYING PARTS TIGHTEN LOOSE FITTINGS RISER HARDWARE TO BE 1/4" MINIMUM RECEPTACLE COVERS TO BE WEATHERPROOF WETHER OR NOT PLUGGED INTO 406.8 CORRECTLY IDENTIFY UNGROUNDED CONDUCTORS # 8 NM CABLE TO HAVE BREAKER AMPACITY SIZED PER 334.80 A MAIN BREAKER IS EEDED PER 25.31 & 225.32 ALSO A GROUNDING ELECTRODE SYSTEM TIGHTEN LOOSE CONNECTORS TO JUNCTION BOX. ALL CABLES TO BE SECURED TO BOX. SUPPORT CABLES WITHIN 12" OF BOX GROUND JUNCTION BOX. CHASE NIPPLE NOT AN APPROVED FITTING WITH CONDU??? VERIFY DERATING OF CIRCUITS PER 310.15 |