Permit: T05EL01173

Parcel: 14021006B


Addresses:

5521 S PARK AV #08


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01173

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/23/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/22/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* DO NOT COVER ENTIRE CIRCUIT BREAKER PANEL, ONLY THE EXPOSED WIRING
06/13/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1. THE 100A CIRCUIT BREAKER TO LARGE FOR FEEDER. 2. THE FEEDER MUST BE AN APPROVED MH CORD TO UNIT FROM SERVICE. 3. KITCHEN EXHAUST FAN CANNOT BE WIRED IN ZIP CORD. 4) COOLER SWITCH WIRING AND RECEPTACLES TO BE IN APPROVED BOXES. 5. INSTALL BATTERIES IN SMOKE DETECTORS. 6. ISOLATE GROUNDS AND NEUTRALS IN SUB PANELS. ALSO BLANK OFF OPEN BREAKER SLOTS. 7. PHYSICALLY PROTECT OPEN WIRING BY PANEL.