Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL01173
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/23/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
06/22/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* DO NOT COVER ENTIRE CIRCUIT BREAKER PANEL, ONLY THE EXPOSED WIRING |
|
06/13/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE 100A CIRCUIT BREAKER TO LARGE FOR FEEDER. 2. THE FEEDER MUST BE AN APPROVED MH CORD TO UNIT FROM SERVICE. 3. KITCHEN EXHAUST FAN CANNOT BE WIRED IN ZIP CORD. 4) COOLER SWITCH WIRING AND RECEPTACLES TO BE IN APPROVED BOXES. 5. INSTALL BATTERIES IN SMOKE DETECTORS. 6. ISOLATE GROUNDS AND NEUTRALS IN SUB PANELS. ALSO BLANK OFF OPEN BREAKER SLOTS. 7. PHYSICALLY PROTECT OPEN WIRING BY PANEL. |