Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/15/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/22/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 02/07/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*SEPERATE GROUNDS AND NEUTRALS IN GUEST HOUSE SUB PANLE NEC. 250.32 BU IDENTIFY WHITE CONDUCTORS USED AS HOT'S CORRECTLY IDENTIFY BRANCH CKT'S IN PANEL DIRECTORY MULTIWIRE BRANCH CKT'S NED TO BE ON OPPOSITE PHASES INSTALL SCREWS FOR PANEL DEAD FRONT COVER FINISH ALL INTERIOR WIRING CONDUCTORS IN RACEWAY MORE THAN 24" NEED DERATED NEC 310.15 |
|
| 11/23/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |