Inspection Status: Partial Approval
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2005 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* CALL FOR FINAL WHEN CUTOVER IS COMPLETE. | |
| 06/22/2005 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CLEAN PAINT AT WATER BOND CONNECTOR OF OF WATER PIPE. 2) NEUTRAL NEEDS GROUNDING ELECTRODE CONDUCTOR TERMINATED DIRECTLY TO NEUTRAL W/OUT SPLICE ( VIA GROUNDING BUS). 3) BOND SCREW IS MISSING AT NEUTRAL BUS @ 100AMP DISC. 4) WHERE IS GAS BOND LOCATION. |