Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 06/28/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR 1) RECALL AFTER CROSS OVER | |
| 06/27/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) BOND JUMPER TO BE SIZED PER 250.102. & 250.66 2) TIGHTEN 2ND GROUND ROD CLAMP | |
| 06/23/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* |