Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T05EL01161
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2005 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
06/13/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CALL TEP TO UNLOCK BREAKER BOX 50 NEW #4 GROUND CAN BE RUN INTO BRAKER BOX .2. SEAL 1" HOLE BOTTOM OF PANEL. 3. ONCE TEP UNLOCKS-INSTALL CIRCUIT BREAKER COVER MISSING. 4. REMOVE DOUBLE LUGGING AT DISCONNECT WITH OUT FUSES-EITHER INSTALL FUSES OR SPLICE STRAIGHT THUR, AND PLUG HOLE ON DISCONNECT. 5. STRAP NEW GROUND TO WALL BELOW SERVICE. |