Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/30/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) AFTER CHANGE OVER INSTALL APPROVED J-BOX WHERE OLD SERVICE IS AND STRAP ALL GROUND WIRES
06/29/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/21/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) AN ADDRESS LABEL IS NEEDED FOR SERVICE. 2) RISER HARDWARE TO BE 1/4" MINIMUM. 3) PLEASE STRAP GROUNDING ELECTRODE CONDUCTOR TO BUILDING. 4) ALL STRANDS OF CONDUCTORS TO BE TERMINATED UNDER TERMINAL LUG. 5) WHITE CONDUCTOR CANNOT BE USED AS A GROUND CONDUCTOR 250-119. 6) OLD DISCONNECT CANNOT BE USED AS A JUNCTION BOX USE AN APPROVED JUNCTION BOX. 7) GROUND JUNCTION BOXES-4 SQ. 8) PLEASE VERIFY WATER & GAS BONDING AS PER CODE.