Inspection History Details
Inspection Status: Not ready for Inspection
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/30/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) AFTER CHANGE OVER INSTALL APPROVED J-BOX WHERE OLD SERVICE IS AND STRAP ALL GROUND WIRES |
|
| 06/29/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/21/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) AN ADDRESS LABEL IS NEEDED FOR SERVICE. 2) RISER HARDWARE TO BE 1/4" MINIMUM. 3) PLEASE STRAP GROUNDING ELECTRODE CONDUCTOR TO BUILDING. 4) ALL STRANDS OF CONDUCTORS TO BE TERMINATED UNDER TERMINAL LUG. 5) WHITE CONDUCTOR CANNOT BE USED AS A GROUND CONDUCTOR 250-119. 6) OLD DISCONNECT CANNOT BE USED AS A JUNCTION BOX USE AN APPROVED JUNCTION BOX. 7) GROUND JUNCTION BOXES-4 SQ. 8) PLEASE VERIFY WATER & GAS BONDING AS PER CODE. |