Permit: T05EL01136

Parcel: 112074050

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/08/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK TO CLEAR INCREASE
08/02/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) GROUND EQUIP GROUND FEEDING IN J-BOX AT LEFT OF SERVICE
2) #8 WIRE TO SMALL FOR 60 AMP BREAKER
3) GROUND RODS NEED TO BE INSTALLED AT THE NEAREST POSSIBLE LOCATION OF SERVICE #4 BARE RUN THRU ATTIC TO EAST END OF HOUSE TO GROUND RODS WOULD BE A POTENTIAL FIRE HAZARD IN THE EVENT OF A LIGHTING STRIKE. SEE ARTICLE 250-NEC