Permit: T05EL01122

Parcel: 11003098C

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01122

Inspection Description - ELECTRIC - FINAL

Inspection Status - Partial Approval

Date Description Inspector Results Comments
06/28/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/20/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) ONLY (1) ONE CONDUCTOR PER TERMINAL LUG. 2) SEAL ENTRANCES ABOVE CURRENT CARRING PARTS. 3) TIGHTEN LOOSE FITTINGS. 4) SUPPORT SEAL TILE AND CONDUITS AS PER CODES. 5) PLEASE EXPOSE NEW UNDER GROUND PVC FOR INSPECTION. 6) COVERS TO BE WEATHERPROOF WEATHER OR NOT PLUGGED IN 408.6. 7) PLEASE VERIFY GAS & WATER BONDING 8) A MAIN DISCONNECTION MEANS IS NEEDED AT SECONDARY B???. 9) DISCONNECTING MEANS NOT TO BE ABOVE 6" 7"