Permit: T05EL01099

Parcel: 117062860


Addresses:

236 N 3RD AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/28/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/22/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The service entrance is not per code.| 215* 1) PROVIDE EVIDENCE THAT THE RISER SERVICE CONDUCTORS ARE " SUNLIGHT RESISTANT" SEE NEC ART 310 -8 (D) " MUST BE LISTED OR MARKED & LISTED" YOU HAVE TWO DIFFERENT INSULATION TYPES ON PHASE CONDUCTORS. 2. AMRK CIRCUITS WITH AREAS OF HOUSE SERVED ( DIRECTORY) 3. FASTENERS FOR PANEL & STRAPS SHOULD BE 1/4" LAG BOLTS & LEAD SHIELDS. SEE TEP SER MANUAL.