Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/10/2011 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 08/05/2005 | ELECTRIC - SERVICE UPGRADE | Partial Approval | IVRS - Inspection :* 1) OK TO CLEAR 2) CALL FOR FINAL WHEN CUT OVER AND CONNECTION OF BRANCH CIRCUITS ARE COMPLETE |
|
| 07/01/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) METER TO BE NO MORE THAN 6'-3" TO CENTER OFF ? FINISHED GRADE PER TEP 2) INSTALL METAL ADDRESS LABEL PER I.R.C. (INTER. RESIDENTIAL CODE) 3) SECURE GROUND ELECTRIC CONDUCTOR BELOW DOOR OPENING (THRESHOLD) 4) CLEAN GAS PIPE CONNECTION AND STRAP CONDUCTOR SECURELY |
|
| 06/27/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ANSWER AT DOOR STILL CANNOT LOCATE WATER BOND. PLEASE LEAVE A MESSAGE AS TO WHERE IT IS. |
|
| 06/09/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. THE CLAMP AT 1ST REBAR CONNECTING THE WIRE TO GAS LINE MUST ALSO HAVE BRASS SCREWS. 2. ITEM # 5 ON YESTERDAY INSPECTION CALLED FOR A WATER LINE BOND-CANNOT LOCATE IT. BOTH ITEMS ON INSPECTION OF 6/8/05 |
|
| 06/08/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |