Permit: T05EL01051

Parcel: 128140940


Addresses:

1008 S BEVERLY AV

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/10/2011 ELECTRIC - SERVICE UPGRADE Approved
08/05/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
1) OK TO CLEAR
2) CALL FOR FINAL WHEN CUT OVER AND CONNECTION OF BRANCH CIRCUITS ARE COMPLETE
07/01/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) METER TO BE NO MORE THAN 6'-3" TO CENTER OFF ? FINISHED GRADE PER TEP
2) INSTALL METAL ADDRESS LABEL PER I.R.C. (INTER. RESIDENTIAL CODE)
3) SECURE GROUND ELECTRIC CONDUCTOR BELOW DOOR OPENING (THRESHOLD)
4) CLEAN GAS PIPE CONNECTION AND STRAP CONDUCTOR SECURELY
06/27/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999* NO ANSWER AT DOOR STILL CANNOT LOCATE WATER BOND. PLEASE LEAVE A MESSAGE AS TO WHERE IT IS.
06/09/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1. THE CLAMP AT 1ST REBAR CONNECTING THE WIRE TO GAS LINE MUST ALSO HAVE BRASS SCREWS. 2. ITEM # 5 ON YESTERDAY INSPECTION CALLED FOR A WATER LINE BOND-CANNOT LOCATE IT. BOTH ITEMS ON INSPECTION OF 6/8/05
06/08/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*