Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* DO NOT REPLACE COOLER IN FRONT OF PANEL |
|
| 05/26/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. 60-AMP FEED COMING INTO PANEL TO HAVE A LOCK NUT. 2. #14 WIRE ON DOUBLE POLE 30 AMP. SHOULD BE ON SINGLE 15 AMP. BREAKER. 3. WHITE WIRE USED AS HOT TO BE COMPLETELY TAPED BLACK, ALSO WIRING RECEPTACLE BEING USED ON THIS CIRCUIT IT'S A 120A RECEPTACLE SHOW BE 240 AMP. 4. NEUTRALS AND GROUNDS CANNOT BE TOGETHER IN THIS SUB-PANEL. 5. CANNOT USE GE BREAKERS IN A SIEMANS PANEL - MUST BE GE. 6. HOLE BOTTOM OF PANEL TO BE SEALED. 7. REMOVE COOLER FROM IN FRONT OF PANEL. |
|
| 05/19/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GATE LOCKED -- 11 AM |
|
| 05/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/15/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. CONDUIT RUNNING INTO MAIN SERVICE SCH 40 PVC CANNOT USE SCH 40 OUTSIDE. 2. CARPORT PANEL CANNOT BE BLOCKED, MARK PANEL CARPORT AND ALSO CIRCUITS 8 &10 CARPORT PANEL. |
|
| 08/16/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/09/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CANNOT USE PVC SCHEDULE 40 ABOVE GROUND MUST BE SCHEDULE 80 2) ENTRY OF 3/4" PVC AT BOTTOM OF PANEL INCORRECT 3) USE FILLER BLANKS FOR EMPTY BREAKER SLOTS 4) TAPE BLACK WIRE USED AS NEUTRAL WHITE ABOVE 5) CANNOT GO INTO WALL WITH LIQUID TIGHT CONDUIT-NEEDS PHSYICAL PROTECTION 6) CANNOT CUT STRANDS ON WIRE USED IN #4 SINCE SERVICE RELEASED FOR ENGERGIZING ALL WORK ABOVE INSTALLED AFTER RELEASE NOTIFY ELECTRICAL CONTRACTOR TO MAEK CORRECTIONS ASAP WILL FOLLOW UP IN 5 DAYS 7) INSTALL CIRCUIT NAMES ON SUB-PANEL INSIDE |
|
| 07/14/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR FOR CHANGE OVER FOR METER #2 | |
| 07/08/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio VERIFY L-11 LICENSED CONT DOING WORK NAME PH# NOTES: 1) GAS BOND TO BE ON CUSTOMER SIDE OF METER. 2) INSTALL MAIN BREAKER AS PER LISTING OF PANEL 3) WHAT IS THE WIRING IN THE 4X4 GUTTER FOR ? WORK OHER THAN METER INSTALL MUST BE APPROVED THRU PLAN CHECK 201 N. STONE & ADDED TO THIS PERMIT |
|
| 06/29/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* CORRECTIONS: 1. YOU MUST INSTALL ANOTHER NEW GROUND ROD TO SERVE THE NEW ELECTRICAL SERVICE. WE DO NOT ACCEPT OLD RODS OR OTHER ELECTRODES. THESE ARE CONSIDERED " UNPROVEN". 2. SCRAPE OR WIRE BRUSH THE PAINT OFF THE WATER PIPE. WHERE CLAMP IS ATTACHED. DO NOT PUT ANY OTHER WIRES ON OR UNDER THE NEW CLAMP. 3. EXTEND THE GROUND WIRE TO THE BUILDING SIDE OF THE GAS SERVICE PIPE. 4) YOUR METER MAIN LOAD CENTER IS RESIDENTIAL GRADE. AND MAY NOT BE ACCEPTABLE TO TEP. CHECK WITH TEP ABOUT THIS. |