Permit: T05EL01030

Parcel: 10711310A


Addresses:

3013 N 1ST AV #02

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/31/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
DO NOT REPLACE COOLER IN FRONT OF PANEL
05/26/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. 60-AMP FEED COMING INTO PANEL TO HAVE A LOCK NUT.
2. #14 WIRE ON DOUBLE POLE 30 AMP. SHOULD BE ON SINGLE 15 AMP. BREAKER.
3. WHITE WIRE USED AS HOT TO BE COMPLETELY TAPED BLACK, ALSO WIRING RECEPTACLE BEING USED ON THIS CIRCUIT IT'S A 120A RECEPTACLE SHOW BE 240 AMP.
4. NEUTRALS AND GROUNDS CANNOT BE TOGETHER IN THIS SUB-PANEL.
5. CANNOT USE GE BREAKERS IN A SIEMANS PANEL -
MUST BE GE.
6. HOLE BOTTOM OF PANEL TO BE SEALED.
7. REMOVE COOLER FROM IN FRONT OF PANEL.
05/19/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
GATE LOCKED -- 11 AM
05/17/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/15/2006 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. CONDUIT RUNNING INTO MAIN SERVICE SCH 40 PVC CANNOT USE SCH 40 OUTSIDE.
2. CARPORT PANEL CANNOT BE BLOCKED, MARK PANEL CARPORT AND ALSO CIRCUITS 8 &10 CARPORT PANEL.
08/16/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/09/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CANNOT USE PVC SCHEDULE 40 ABOVE GROUND MUST BE SCHEDULE 80
2) ENTRY OF 3/4" PVC AT BOTTOM OF PANEL INCORRECT
3) USE FILLER BLANKS FOR EMPTY BREAKER SLOTS
4) TAPE BLACK WIRE USED AS NEUTRAL WHITE ABOVE
5) CANNOT GO INTO WALL WITH LIQUID TIGHT CONDUIT-NEEDS PHSYICAL PROTECTION
6) CANNOT CUT STRANDS ON WIRE USED IN #4 SINCE SERVICE RELEASED FOR ENGERGIZING ALL WORK ABOVE INSTALLED AFTER RELEASE NOTIFY ELECTRICAL CONTRACTOR TO MAEK CORRECTIONS ASAP WILL FOLLOW UP IN 5 DAYS
7) INSTALL CIRCUIT NAMES ON SUB-PANEL INSIDE
07/14/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* OK TO CLEAR FOR CHANGE OVER FOR METER #2
07/08/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
A reinspection fee has been assessed for this inspection. Multiple inspectio VERIFY L-11 LICENSED CONT DOING WORK NAME PH#
NOTES: 1) GAS BOND TO BE ON CUSTOMER SIDE OF METER. 2) INSTALL MAIN BREAKER AS PER LISTING OF PANEL 3) WHAT IS THE WIRING IN THE 4X4 GUTTER FOR ? WORK OHER THAN METER INSTALL MUST BE APPROVED THRU PLAN CHECK 201 N. STONE & ADDED TO THIS PERMIT
06/29/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* CORRECTIONS: 1. YOU MUST INSTALL ANOTHER NEW GROUND ROD TO SERVE THE NEW ELECTRICAL SERVICE. WE DO NOT ACCEPT OLD RODS OR OTHER ELECTRODES. THESE ARE CONSIDERED " UNPROVEN". 2. SCRAPE OR WIRE BRUSH THE PAINT OFF THE WATER PIPE. WHERE CLAMP IS ATTACHED. DO NOT PUT ANY OTHER WIRES ON OR UNDER THE NEW CLAMP. 3. EXTEND THE GROUND WIRE TO THE BUILDING SIDE OF THE GAS SERVICE PIPE. 4) YOUR METER MAIN LOAD CENTER IS RESIDENTIAL GRADE. AND MAY NOT BE ACCEPTABLE TO TEP. CHECK WITH TEP ABOUT THIS.