Permit: T05EL01010

Parcel: 12605074A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL01010

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
06/16/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/23/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* / OLD INSPECTION WAS WRONG BLDG. 1) PLEASE POST SUITE NUMBER AS ADDRESSED ON PERMIT OR REVISE PERMIT TO MATCH SERVICE. 2) PLEASE VERIFY PERMIT FOR NEW WALL AND ELECTRIC FOR INSTALLATION INSPECTIONS. 3) CORD NOT ALLOWED AS PERMANENT WIRING METHOD.
05/19/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
1) ADDRESS TO BE POSTED ON BLDG AND SERVICE
2) UNIT LOCKED-NEED INTERIOR ACCESS
3) WE HAVE EXPOSED CONDUCTOR ON OUTSIDE OF BLDG AND EXPOSED CABLES AT A/C UNITS
4) SERVICE CONDUCTORS DETERIORATED
5) SERVICE MAIN BONDING JUMPER NOT SIZED PER CODE