Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/21/2005 | ELECTRIC - SERVICE UPGRADE | Approved | ||
| 06/08/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/25/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/18/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999*NOTES: CALLED, LEFT MSG PER REQUEST. 1) GROUND RODS CANNOT EXCEED 45 DEGREE ANGLE 2) BOND GAS PIPING. 3) IMPROPER GROUND CLAMPS ON GROUND RODS. LOOSE, USE ACORN TYPE. 4) NEW WIRING FOR INTERIOR MUST BE PERMITTED, & INSPECTED. THERE IS ALSO A RE-CONNECT PERMIT ISSUED SEE NOTES. |