Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/27/2005 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 06/23/2005 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL 2 1/2" IMC OR RIGID METAL RISER 2) 90 DEGREE BEND IS NOT ACCEPTED AT RISER ( GET W/TEP FOR THEIR REQUIRED SPECIFICATIONS) 3) INSTALL METAL ADDRESS TAG AT SERVICE PER TEP AND INTER. RE?? CODE 4) INSTALL 2ND GROUND ROD PER NATIONAL ELECT CODE 5) BOND GAS LINE PER NEC 6) INSTALL WATER BOND PER NEC |