Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00982
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/27/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
04/21/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GATE IS LOCKED, NO ONE HERE. |
|
07/12/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR UPGRADE. CALL FOR FINAL ONCE EXISTING 100 SERVICE DISCONNECT TO BE REMOVED AN APPROVED W/PROOF J BOX FOR SPLICE | |
07/01/2005 | ELECTRIC - FINAL | Cancelled | ||
07/01/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
06/07/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* CORRECTIONS REQUIRED. 1. NIPPLES OR FITTING WHICH CONTAIN UNFUSED SERVICE ENTRANCE CONDUCTORS MUST BE FITTED WITH A GROUNDED BUSHING ON BOTH ENDS. 2. THE GUTTER MUST HAVE A SEALABLE SCREW ON THE LEFT END SEAL SLOT. 3. THE PLATFORM MUST BE OF A PERMANENT CONSTRUCTION. IT CANNOT BE REMOVABLE. THE SERVICE DISCONNECTS MUST ALWAYS BE READILY ACCESSIBLE. THE PLATFORM MUST BE NOT LESS THAN THREEE ( 3FT) IN WIDTH- MEASURED FROM THE FRONT OF THE SERVIDE EQUIPEMENT. |