Permit: T05EL00973

Parcel: 136220220


Addresses:

7602 E 38TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/23/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
06/14/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NEED ANTIOXIDATON PASTE ON ALL ALUM TERMINATIONS. 2) SECURE CARFLEX AT A.C (GET A.C PERMIT). 3) ALUM-COPPER SPLICE IS ILLEGAL S YOU HAVE INSTALLED ( USE AN APPROVED COPPER TO AL. SPLICE DEVICE AND INSTALL CORRECT SIZED CONDUCTOR. ( THIS IS A NEUTRL DO NOT SIZE LESS THAN 50 AMPS. 4) WHERES WATER BONDED AT?