Permit: T05EL00956

Parcel: 107110200

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/16/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/12/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1) CHASE NIPPLES ARE NOT TO BE USED TO CONNECT FITTINGS SUCH AS L b's, 'T's', OUTLET BOXES ETC... TO PANELS OR SERVICE ENCLOSURES. THEY HAVE BEEN FOUND TO NOT PROVIDE A GOOD PATH TO GROUND DUE TO THEIR BEVELED SHOULDER DESIGN
2) LOAD SIDE CONDUCTORS CANNOT BE INSTALLED IN GUTTER ALONG WITH SERVICE CONDUCTORS. SEE NEC 230.7. YOU HAVE TWO SETS OF LOAD CONDUCTORS FROM DISCONNECTS THRU THE SERVICE CONDUCTOR GUTTER