Permit: T05EL00953

Parcel: 140230760


Addresses:

5841 S MORRIS BL

Inspection Status: Partial Approval

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/17/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*OK TO CLEAR INC. CALL FOR FINAL AFTER TIE IN
05/13/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) IMPROPER FITTING USED ON LB TERMINATION INTO PANEL. USE CLOSE NIPPLE WITH LOCKNUTS & BUSHING, PIPE CONNECTOR NOT APPROVED