Permit: T05EL00915

Parcel: 120080900


Addresses:

4503 S 12TH AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/12/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/10/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) INSTALL PERMANENT ADDRESS LABEL ON SERVICE ENCLOSURE. 2) INSTALL BOND BUSHING AT 1" TERMINATION WHERE USING RE WASHERS. 3) SUPPORT RISER WITHIN 3' OF PANEL, USE 1/4" BOLTS 4) STRAP #4 BARE TO WALL.