Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/31/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/26/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) CONNECT RISER 2) BREAKER TO BE LISTED FOR USAGE BY MANUFACTURER 3) WE HAVE MULTIPLE TERMINATIONS AT GROUNDS INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS LABEL 4) ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINIUM CONDUCTORS 5) A SEALING DEVICE IS NEEDED ABOVE CURRENT CARRING PARTS 6) TIGHTEN LOOSE FITTINGS AND USE APPROVED ELECTRICAL PVC TO CONNECT ALL JOINTS 7) AN APPROVED BUSHING IS NEEDED AT BACK OF PANEL FOR CONDUCTORS/CABLES 8) SUPPORT CONDUIT ABOVE PANEL |