Permit: T05EL00901

Parcel: 134040800


Addresses:

610 S MOUNTVALE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/31/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/26/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1) CONNECT RISER
2) BREAKER TO BE LISTED FOR USAGE BY MANUFACTURER
3) WE HAVE MULTIPLE TERMINATIONS AT GROUNDS INSTALL GROUNDING EQUIPMENT CONDUCTORS AS PER MANUFACTURERS LABEL
4) ANTI-OXIDE COMPOUND NEEDED ON ALL ALUMINIUM CONDUCTORS
5) A SEALING DEVICE IS NEEDED ABOVE CURRENT CARRING PARTS
6) TIGHTEN LOOSE FITTINGS AND USE APPROVED ELECTRICAL PVC TO CONNECT ALL JOINTS
7) AN APPROVED BUSHING IS NEEDED AT BACK OF PANEL FOR CONDUCTORS/CABLES
8) SUPPORT CONDUIT ABOVE PANEL