Permit: T05EL00895

Parcel: 127121500


Addresses:

5732 E 6TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
06/30/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
1) OK TO CLEAR UPGRADE-WILL NOTIFY TEP
2) CLEARED TO OFFICE 6/30./05 1:20 PM
05/12/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) PLEASE VERIFY CONDUCTOR SIZE FOR SUB-PANEL. THERE ARE NOT MARKING ON CONDUCTOR. ALSO BLUE WIRE NUTS HAVE A MAXIMUM SIZE LISTING #6
2) PLEASE IDENTIFY NEUTRAL CONDUCTOR AT TERMINAL LUG
3) WATER BOND TO BE INTERIOR SIDE OF UNIONS AND VALVES