Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/13/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 05/02/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*NOTES: 1) COOLER NOT WIRED PER CODE, MUST HAVE APPROVED W/P J-BOXES, RECEPTACLES, W/P COVERS, APPROVED CORDS FOR PUMP & MOTOR. 2) WIRING FROM SERVICE OVER CURRENT TO M.H NOT TO CODE, USE PROPER CABLE & CORD CAP, OR HARD WIRE TO CODE, NO EXPOSED SPLICES. 3) EXPOSED WIRING FOR OUTSIDE RECEPTS UNDER M.H AND ALONG EAST SIDE NOT PER CODE. 4) NEED ACCESS INSIDE UNIT FOR INSPECTION, BE SURE THERE ARE SMOKE DETECTORS IN BEDROOMS, NO EXPOSED WIRING , ALL DEVICES & COVERS INTACT. INSPECTOR CALLED APPLICANT PER MSG. REQUEST. NO ANSWER, LEFT MSG. ALL WORK TO BE DONE BY LICENSED CONTR. VERIFY NAME & PH #. RE CALL INSPECTION. |