Inspection History Details
Permit: T05EL00883
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/02/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* THE #4 COPPER WIRE FROM THE GROUND RODS IS ONLY CONNECTED TO THE PEDESTAL ENCLOSURE IN THE BACK-SINCE THIS IS A SERVICE IT ALSO NEEDS TO CONTINUE ON THE NEUTRAL INSTALL A JUMPER FROM GROUND LUG TO NEUTRAL. |