Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK TO CLEAR INCREASE |
|
| 08/22/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PANEL ENTRIES NEED TO BE WEATHERPROOF (MYERS HUB OR EQUAL) 2) EXPOSE GROUND RODS 3) INSTALL W.P. K.O SEAL 4) RESCHEDULE AFTER PERMIT |
|
| 05/05/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* THERE ARE TOOO MANY BUILDING CODE VIOLATIONS ON THE PROPERTY THAT CAUSE ME TO DENY CONNECTION OF THE NEW SERVICE GEAR. |
|
| 04/29/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* 1. INSTALL ADDRESS ABOVE OR BELOW METER SOCKET. USE EMBOSSED METAL STRIP. DO NOT USE PENCIL, PEN " MAGIC MARKER", SHARPIE, SPRAY PAINT OR CRAYON. 2. USE ROD CLAMPS TO ATTACH GROUNDING CONDUCTOR TO GROUND RODS. 3. USE A BRACE KIT OR MINNERALLAC STRAP FOR BRACE ON RISER PIPE. REMOVE FROM SERVICE DRO CLEVIS. CORRECT & RECALL. PLEASE HAVE A COPY OF THE BUILDING PERMIT FOR THE ROOM ADDITION TO THE HOUSE- WITH THIS PERMI ON NEXT INSPECTION. THANKS |