Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/12/2005 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 05/03/2005 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE. 110.26 2) WEATHER PROOF COVER TO BE WEATHER PROOF WETHER OR NOT PLUGED INTO 406.8. 3) GROUNDING EQUIPMENT CONDUCTORS TO BE INSTALLED AS PER MANUFACTURERS INSTRUCTIONS. 4) A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS. 5) ANTI OXIDE COMPOUND IS NEEDED ON ALL ALUMINUM TERMINATIONS. 6) METER SECTION IS SEALED WITHOUT A CLEARANCE UNABLE TO INSPECT. 7) PLEASE VERIFY GAS & WATER BONDING |
|
| 04/29/2005 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |