Permit: T05EL00875

Parcel: 110160350


Addresses:

2444 N SONOITA PL

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/12/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/03/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) MAINTAIN WORKING CLEARANCE IN FRONT OF SERVICE. 110.26 2) WEATHER PROOF COVER TO BE WEATHER PROOF WETHER OR NOT PLUGED INTO 406.8. 3) GROUNDING EQUIPMENT CONDUCTORS TO BE INSTALLED AS PER MANUFACTURERS INSTRUCTIONS. 4) A SEALING DEVICE IS NEEDED FOR ENTRANCES ABOVE CURRENT CARRING PARTS. 5) ANTI OXIDE COMPOUND IS NEEDED ON ALL ALUMINUM TERMINATIONS. 6) METER SECTION IS SEALED WITHOUT A CLEARANCE UNABLE TO INSPECT. 7) PLEASE VERIFY GAS & WATER BONDING
04/29/2005 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*