Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/25/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/22/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210* BE ADVISED: THE UPPER FOUR (4) CIRCUIT BREAKERS POSITIONS ARE LOCATED ABOVE SIX FEET SEVEN INCHES ( 6" 7") FROM NATURAL GRADE. PER NEC ART. 407.8 THESE POSITIONS MUST BE PERMANENTLY BLOCKED FROM FUTURE USE. CORRECT AND RECALL. |