Permit: T05EL00817

Parcel: 10603033A


Addresses:

115 E MOHAVE RD #01


Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T05EL00817

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
04/27/2005 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
04/25/2005 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The bonding is not per code.| 235* 1. THE GROUNDING ELCRODE(S) MUST BE LOCATED IN THE SAME AREA AS THE GROUNDING ELECTRODE CONDUCTOR CONNECTION TO THE SYTEM. SEE NEC ART 250-30(4) YOU WILL HAVE TO INSTALL TWO NEW GROUND RODS IN THE SAME AREA A THE SERVICE PANELS AND RUN A GROUNDING ELECTRODE CONDUCTOR FROM ROD TO ROD TO PANELS. THE OTHER GROUNDING CIRCUIT MAY BE LEFT IN PLACE. THANKS. RECALL INSPECTION