Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE RELOCATION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2005 | ELECTRIC - SERVICE RELOCATION | Approved | IVRS - Inspection :* | |
| 11/08/2005 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/30/2005 | ELECTRIC - SERVICE RELOCATION | Not ready for Inspection | IVRS - Inspection :* 1) GFI COVER TO BE WEATHER PROOF WETHER OR NOT PLUGED INTO 408.6 2) PROPERLY MOUNT GFI OUTLET BOX AND TIGHTEN NIPPLE FITTING 3) CHASE NIPPLE NOT AN APPROVED FITTING FOR LB 4) GROUND CONDUCTOR TO BE GREEN ENTIRE LENGTH 250.119 AND CLEAN SURFACE UNDER LUG 250.12 |
|
| 04/21/2005 | ELECTRIC - SERVICE RELOCATION | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) THE ELECTRICAL SERVICE REQUIRES 36" CLEAR IN FRONT OF IT THE TREE IS APPROX 29" IN FRONT OF 2002 NEC 110-26 2) PLAN STATES ADDITIONAL PERMITS FOR PHOTO VOLTAICS REQUIRED-NON ON SITE AND SYSTEM IS INSTALLED AND RUNNING 3) USE A ROMEX FITTING TO BRING GROUND WIRE THRU AT BOTTOM OF SERVICE 4) KEARNEY SPLICE GOOD FOR WIRE TO WIRE SPLICE ONLY NOT WIRE TO 2 WIRE SPLICE-NEUTRAL MUST BE FULL SIZE 5) PROVIDE A PERMIT AND PLAN FOR SYSTEM TO BE INSPECTED 6) PROVIDE LADDER TO INSPECT ROOF 7) SUB-PANEL HAS HOLE ON BOTTOM AND OPEN BREAKER SLOT 8) WHITE WIRES RECONNECTED TO BREAKERS MUST BE TAPED BLK OR RED 9) NEW CIRCUITS WIRED INTO HOUSE OUT OR THIS PANEL NOT ON PERMIT 10) SUPPORT PVC AND LB ON NORTH SIDE OF PANEL AND NEW J-BOX MUST HAVE GROUND TO PANEL 11) SUB-PANEL CANNOT HAVE GROUNDS AND NEUTRALS COMBINED MUST BE SEPERATED 12) OLD CIRCUIT BREAKER FOR NEW DRYER-CANNOT VERIFY IT'S CUTLER HAMMER 13) CLEARANCE IN FRONT OF SUB-PANEL REQUIRED PER 2002 NEC 110.26 14) FINISH MARKING ALL CIRCUITS IN MARKER NOT PENCIL |