Permit: T05EL00797

Parcel: 116127050

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/26/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR
04/22/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* CORRECTIONS REQUIRED. 1. THE OVAL HOLE CUT IN THE BOTTOM OF THE METER CAN WILL REQUIRE A METAL PLATE BELOW AND ABOVE THE RISER CONDUIT TO COVER THE HOLE. LOCKNUTS ARE REQUIRED TOP & BOTTOM. THESE SHOULD BE MADE WRENCH TIGHT. THE REDUCING WASHERS ARE NOT ACCEPTABLE. 2. INSTALL A K.O BLANK TO COVER THE UNEEDED HOLE IN THE METER CABINET. 3. UST TERMINALS TO LAND THE GROUND WIRE ON THE NEUTRAL GROUND BASS. 4. THIGHTEN ACORN CLAMP AT GRD.ROD & EXPOSE GRD ROD ENDS. 6. BURY GROUNDING CONDUCTOR 2 T6O 3 INCHES BELOW SURFACE GRADE. SEE NEC ART 110-12 & CAS. RECALL.