Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00790
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/09/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR INC . 1) DRIVE GROUND ROD BY SERVICE FLUSH WITH FINISHED GRADE ( TRIP HAZARD). 2) USE CLAMP TYPE CONNECTOR AT GROUND WIRE TERMINATION INTO SERVICE PANEL. 3) WHERE MORE THAN ONE SERVICE IS INSTALLED ON SOME BLD. THE GROUNDING ELECTRODE SYSTEMS SHALL BE TIED TOGETHER TO FORM ONE GROUNDING SYSTEM. PER 250-58 NEC |