Permit: T05EL00775

Parcel: 128111230


Addresses:

4726 E COOPER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/17/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/09/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* NOTES: NO COMPLIANCE WITH NOTES INSPE. ON 4/27/05
05/02/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920* NO ANSWER AT DOOR. RE-CALL INSPECTION WHEN SOMEONE HOME OR LEAVE GATE OPEN.
04/27/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* OK TO CLEAR SERV UPGRADE. 1) #8 CONDUCTOR NEEDS TO BE ON A 50 AMP CIRCUIT BREAKER NOT 60. 2) GFI RECEPTACLE IS NOT SCREWED INTO THE JUNCTION BOX PROPERLY