Permit: T05EL00762

Parcel: 134243870


Addresses:

6338 E COLGATE DR

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/04/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/26/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 30 AMP CIRCUIT BREAKER FOR A/C THE #6 WIRES ARE TO LARGE TO BE SET IN CIRCUIT BREAKER TERMINALS. LARGEST ALLOWED ARE #10-USE A STAKON OR SPADE OR FORK ON #6 OR WIRE NUT AND REDUCE TO #10
2) LAST INSPECTOR ASKED FOR VERIFICATION OF A/C PERMIT-HAVE IT ON SITE
3) ITEM #8 SUPPORT GROUND TO RODS, OK NOW SUPPORT BOND TO GAS LINE
4) OPENING USED TO ENTER GAS BOND TO BIG
04/19/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NEED MECHANICAL CONTRACTOR TO OBTAIN PERMIT. 2) DRIVE RODS FLUSH OR BELOW GRADE. 3) BOND GAS & WATER PIPING TO SERVICE 4) INSTALL PERMANENT LABEL PER TEP ON ELEC SERVICE & PER IRC. 5) SECURE A.C CONDUIT PER NEC. 6) SEE DETAING REQUIREMENTS IN ART. 310 FOR COMBINED HOME RUNS AND CORRECT ACCORDINGLY. 7) LABEL ALL CIRCUITS. 8) BURY & SUPPORT G. ELECTRODE CONDUCTOR.