Permit: T05EL00748

Parcel: 129054100


Addresses:

2101 E 19TH ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/28/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/15/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) ONE INCH CONDUIT ABOVE PANEL NOT SUPPORTED 2. ONE INCH CONDU?? FITTING ABOVE PANEL MAKED ?? ENTRY INTO PANEL, ROMEX CONDUCTORS UNPROTECTED AT CONDULET EXIT AND PANEL ENTRY. 3) IMPROPER TO ROMEX ENTRY AT TOP OF PANEL 4) OPEN BREAKER SLOTS TO BE COVERED. 5) WIRING TO COMPRESSOR AT WEST WALL TO BE PROPERLY INSTALLED IN CONDUIT. PLEASED CORRECT & RECALL.