Permit: T05EL00744

Parcel: 130123390


Addresses:

3533 E 32ND ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/20/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK TO CLEAR INC
04/14/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*NOTES: 1) 2 GROUND RODS REQUIRED 6' MIN. APART. 2) BOND WATER & GAS PIPING. 3) ALL CIRCUIT BREAKERS MUST BE SAME MANUFACTURERS A PANEL. 4) ID CIRCUIT BREAKERS. 5) STAP # 4 BARE TO WALL. 6) INSTALL BUSHING IN BACK KNOCKOUT TO PROTEXT WIRING EXITING PANEL.