Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T05EL00698

Parcel: 126040880


Addresses:

650 N CATALINA AV

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/26/2005 ELECTRIC - FINAL Approved IVRS - Inspection :* OK FINAL
04/20/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) LABEL ALL BREAKERS. 2) PLEASE VERIFY USAGE OF BLUE WIRE NUTS FOR CONDUCTORS LARGER THAN #8. 3) PLEASE ADD CIRCUITS FOR NEW ELECTRIC TO DRYER AND WELDER.
04/19/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) SERVICE DROP CONDUCTOR TO BE AS EX #2 230.24 3' FROM SERVICE DROP CONDUCTORS TO ROOF. 2) OK GROUNDING. OK TO CLEAR CALLE TEP MAP ROOM. 2:30