Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T05EL00691
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/12/2005 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :*APPROVED OK TO CLEAR | |
04/08/2005 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection :1) ROMEX EXTENSION CORD IS NOT LEGAL AS WIRED PLEASE REPLACE PER NEC OR REMOVE ALTOGETHER 2) PROPERLY WIRE TRANSFORMER AT LAUNDRY ROOM. 3) INTALL BLANK PLATE OVER EXPOSED WIRES @ LAUNDRY ROOM J-BOX ( SWITCH LOCATION) OR INSTALL SWITCH & PLATE. 4) INSTALL MISSING DEVICE PLATES THROUGH OUT. 5) GROUNDING RECEPTACLES NOT ALLOWED ON UNGROUNDED CIRCUITS UNLESS GFCI PROTECTED 6) REPLACE DAMAGED RECEPTACLES. 7) INSTALL SMOKE DETECTORS IN HALLWAY. 8) LIGHT BOX @ S.WEST BEDROOM NEEDS A LIGHT FIXTURE OR BLANK PLATE. |