Permit: T05EL00683

Parcel: 133121640


Addresses:

7740 E CLARENCE PL

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
04/19/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/15/2005 ELECTRIC - FINAL Partial Approval IVRS - Inspection :* 1) ONLY ONE CONDUCTOR PER LUG/TERMINAL. 2) PLEASE FINISH 5 & 6 OF PREVIOUS INSPECTION. OK TO CLEAR CALLED TEMP MAP ROOM 1:05
04/14/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :* 1) NEED BOND BUSHINGS BOTH SIDES OF SERVICE NIPPLE AND REDUCING WASHER AT BROKEN CONCENTRICS. 2) NEED A GROUNDING ELECTRODE SYSTEM WITH GAS AND WATER BONDS. 3) CHASE NIPPLES NOT AN APPROVED FITTING. 4) BOND PANEL ENCLOUSER. 5) FILL UNUSED OPENING AT CABLE ENTRANCES W BACK OF PANEL WITH A FIRE RETARDANT PRODUCT. 6) SEALING DEVICES ARE NEEDE ABOVE CURRENT CARRYING PARTS. 7) PLEASE SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND REAPRI CUT ALUMINUM GROUDING CONDUCTOR.