Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 04/19/2005 |
ELECTRIC - FINAL |
|
Approved |
IVRS - Inspection :* |
| 04/15/2005 |
ELECTRIC - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) ONLY ONE CONDUCTOR PER LUG/TERMINAL. 2) PLEASE FINISH 5 & 6 OF PREVIOUS INSPECTION. OK TO CLEAR CALLED TEMP MAP ROOM 1:05 |
| 04/14/2005 |
ELECTRIC - FINAL |
|
Not ready for Inspection |
IVRS - Inspection :* 1) NEED BOND BUSHINGS BOTH SIDES OF SERVICE NIPPLE AND REDUCING WASHER AT BROKEN CONCENTRICS. 2) NEED A GROUNDING ELECTRODE SYSTEM WITH GAS AND WATER BONDS. 3) CHASE NIPPLES NOT AN APPROVED FITTING. 4) BOND PANEL ENCLOUSER. 5) FILL UNUSED OPENING AT CABLE ENTRANCES W BACK OF PANEL WITH A FIRE RETARDANT PRODUCT. 6) SEALING DEVICES ARE NEEDE ABOVE CURRENT CARRYING PARTS. 7) PLEASE SEPARATE GROUNDING EQUIPMENT CONDUCTORS AND REAPRI CUT ALUMINUM GROUDING CONDUCTOR. |