Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit: T05EL00644

Parcel: 116094240


Addresses:

2905 W SPEEDWAY BL


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL00644

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/15/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/11/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The conduit is not installed per code.| 240* 1) PVC IN PLANTER MUST BE 24" DEEP. 2) PIPE FITTINGS CONDULETS SUCH AS TEC , LB, ETC. ARE NOT ALLOWED TO BE BURIED OR CONCEALED. YOU MUST EITHER USE WATER PROOF/RAIN TITE J BOXES WHICH EXTEND TO THE SURFACE- OR USE TWO RUNS OF CONDUIT TO THE CONTROLLER PAD. ONE IN ONE OUT.