Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00644
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/15/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/11/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The conduit is not installed per code.| 240* 1) PVC IN PLANTER MUST BE 24" DEEP. 2) PIPE FITTINGS CONDULETS SUCH AS TEC , LB, ETC. ARE NOT ALLOWED TO BE BURIED OR CONCEALED. YOU MUST EITHER USE WATER PROOF/RAIN TITE J BOXES WHICH EXTEND TO THE SURFACE- OR USE TWO RUNS OF CONDUIT TO THE CONTROLLER PAD. ONE IN ONE OUT. |