Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* 1) OK FINAL |
|
| 07/20/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) PLEASE RECALL INSPECTION, RICH H. WILL RESPOND |
|
| 07/11/2005 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK TO CLEAR METER 2M. 1) WILL CHECK ON WORK DONE UNDER PREVIOUS INSPECTION | |
| 07/06/2005 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 07/06/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) RISER HARDWARE TO BE 1/4" MINIMUM. 2) BOND GAS TO INTERIOR SID EOF PIPING 3) BREAKERS TO BE LISTED FOR USE BY MANUFACTURE. 4) BOND JUNCTION BOX. 5) INTERIOR NEW CIRCUTI AND WIRING AS PER PLANS HAVE BEEN COVERED WITHOUT INSPECTION. PLEASE UNCOVER TO INSPECT. 6) BOXES WILL BE NEEDED AT LIGHTS. 7) PLANS CALL FOR RECESSED CANS. 8) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING. |