Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00612
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK TO CLEAR WILL NOTIFY TEP | |
04/12/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*1) WHEN YOU INSTALL THE GROUNDING ELECTODE CONDUCTOR IN METAL PIPE, THE OPEN END WHERE # 4 COPPER COMES OUT FO MUST HAVE A CLAMP BONDING THE END OF THE PIPE TO # 4 COPPER WIRE TO REMOVE A CHOKE EFFECT YOU'LL FIND THIS 250 OF 2002NEC. 2) LOOKED ON SHELVES IN STORAGE ROOM COULD NOT LOCATE KEYS TO CHECK J-BOX INSIDE. |