Permit: T05EL00598

Parcel: 117071740


Addresses:

639 S 6TH AV


Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Permit Number - T05EL00598

Inspection Description - ELECTRIC - FINAL

Inspection Status - Denied

Date Description Inspector Results Comments
04/15/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* INSIDE OK AFTER CONSULTING AN ELECTRICIAN I'M SURE YOUR WERE ADVISED TO UPGRADE THE ELECTRICAL SERVICES. THE EXISTING SERVICES ARE OLD AND DETERIORATED THE INSULATION IS CRACKING OF CONDUTORS, THE WIRING IN THE OLD DISCONNECT IS UNSAFE. FOR THE SAFETY OF THE PROPERTY AND OCCUPANTS PLEASE UP GRADE SERVICE.
04/01/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) NEUTRALS & GROUNDS CANNT BE CONNECTED TOGETHER AT SUB PANEL. 2) CONDUIT BRINGING IN FEEDERS TO HAVE A LOCKNUT. 3) TAPE GREEN WITH WHITE TAPE. 4) SERVICE IN A DETERIORATED STATE MUST BE REPLACED. YOU SHOULD CONSIDER ALSO UPGRADING SERVICE TO NEXT DUPLEX. PLEASE CALL ME 909-5184
03/30/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920* UNIT LOCKED MUST BE OPEN FOR INSPECTION. RECALL INSPECTION WHEN ACCESS AVAIL.