Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/04/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/31/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL ANTIOXIDATION PASTE ON ALL ALUM. TERMINATIONS. 2) CLEAN PAINT OFF WATER PIPE WHERE THE BOND CLAMP IS ATTACHED ( WHERE IS GAS BOND AT) 3) DRIVE GROUND RODS FLUSH OR BELOW GRADE AS REQUIRED BY NATIONAL ELEC. CODE |
|
| 03/29/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INSTALL GROUNDING ELECTRODE SYSTEM 2 GROUND RODS, BOND GAS, WATER. 2) INSTALL 2" GROUNDING BUSHING AT PANEL & METER BASE. 3) INSTALL LOCKNUT BETWEEN 3/4" LB & PANEL AT CHASE NIPPLE. 4) ONLY SQ D BREAKERS ARE ACCEPTABLE FOR THIS PANEL. 5) EQUIP. GROUNDING LUGS ARE NEVER ACCEPTED USING SHEET ROCK SCREWS. 6) APPLY ANTI OXIDATION PASTE TO ALL ALUM. TERMINATIONS. 7) SECURE 3/4" CONDUIT BETWEEN PANEL & ROOF. 8) IDENTIFY KITCHEN APPLIANCE CIRCUITS. |