Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00588
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
04/13/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* BE ADVISED, THIS PERMIT COVERS ONLY THE INSTALLATION OF THE NEW SERVICE PANEL AND RECONNECTION OF EXISTING CIRCUITS. ANY NEW WIRING EXTENSIONS IN THE INTERIOR AND EXTERIOR REQUIRE A NEW PERMIT OR A REVISION TO THIS ONE. THANK YOU. | |
03/31/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 2002 NEC 110.26 REQUIRES 3' OF CLEARANCE IN FRONT OF SERVIE DOWN TO GRADE- THE GAS METER INTERFIRES WITH THIS CLEARANCE. 2) SOUTH WEST GAS REQUIREMENTS STATE GAS REGULATOR MUST BE 3' AWAY FROM SERVICE. 3) DRIVE 2ND GROUND ROD FLUSH OR BELOW GRADE. |