Permit: T05EL00587

Parcel: 125121660


Addresses:

3349 E 3RD ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
08/08/2005 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
1) OK TO CLEAR
07/20/2005 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SECURE GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE
2) DRIVE RODS FLUSH OR BELOW GRADE
3) DERATE CONDUCTORS PER TABLE 310.15 (B) (2) A
4) I DON'T SEE WATER OR GAS BOND
5) PROVIDE ATTIC ACCESS
04/29/2005 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*