Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/29/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* ITEM 2) REPAIR IS NOT CORRECTED PROPERLY SELF TAPPING SCREW IS NOT ACCEPTABLE |
|
| 03/25/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) INSTALL BOND BUSHING ON OFF SET NIPPLE AND BOND ENCLOSURE 2) INSTALL BOND JUMPERS FOR NEUTRAL AND GROUND BAR TO ENCLOSURE 3) INSTALL BLANK WHERE BREAKER MISSING 4) INSTALL PERMANENT ADDRESS LABEL ON SERVICE |