Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/31/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 03/29/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) WHEN THE GROUNDING ELECTRODE CONDUCTOR IS HOUSED IN PIPE THE END GOING TO GUTTER MUST HAVE ? CONNECTOR. ALSO END WHERE WIRE COMES OUT OF PIPE- THE END OF PIPE MUST BE BOND TO WIRE. THESE CONNECTIONS REQUIRED IN ORDER TO ELIMINATE A CHOKE POSSIBILITY IN TIME OF FAULT SECTION 250 OF 2002 NEC. 2) PLEASE MAKE OWNER AWARE OTHER GROUNDS TO SERVICES-2524, 2510 OWNERS PANEL, 2530, 2532 |