Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05EL00553
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/05/2005 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/01/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PLEASE TIE UP YOUR DOG & RECALL |
|
| 03/25/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* 1) GATE LOCKED 2) RECALL INSPECTION WHEN ACCESS AVAILABLE |
|
| 03/23/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NOTES: 1) CHANGE ADDRESS ON PERMIT TO CORRECT ADDRESS. 2) INSTALL GROUNDING SYSTEM, 2 GROUND RODS 6" APART, BOND WATER & GAS PIPING. 3) INSTALL PERMANENT ADDRESS LABEL ON SERVICE, MUST BE SCREWED OR RIVITED TO COVER. 4) RISER CONDUIT MUST BE SUPPORTED WITHING 3' OF METER BASE-USE MIN 1/4" BOLTS. 5) I.D CIRCUIT BREAKERS. 6) MAIN BREAKER MUST HAVE ADDITIONAL HOLD DOWN DEVICE PER NEC. |