Permit: T05EL00518

Parcel: 120031130


Addresses:

926 W COLUMBIA ST


Inspection Status: Denied

Inspection History: ELECTRIC - RECONNECT

Permit Number - T05EL00518

Inspection Description - ELECTRIC - RECONNECT

Inspection Status - Denied

Date Description Inspector Results Comments
03/22/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245* NOTES: 1) SMOKE DETECTORS TO CLOSE TO COOLER VENTS-MUST BE 3' OR MORE AWAY FROM REGISTERS. 2) SERVICE IN NEED OF UPGRADE-EXSISTING IS OUTDATED & WEATHER DAMAGE TO DISCONNECT FROM RAIN ENTRY, ALSO SE CABLE USED AS RISER NOT PER CODE
03/18/2005 ELECTRIC - RECONNECT Denied IVRS - Inspection :
There is no access to the site.| 920* HOUSE MUST BE OPEN FOR INSPECTION